Circuit breaker, GoPact MCCB 250B, 3 Poles, 25kA at 415VAC, 250A rating, TMD trip unit, adjustable thermal protection.
Specifications |
Range | GoPact MCCB |
Country of Origin (Estimated) | India |
Warranty | 12 months |
CO/CQ | Yes (if) |
Product name & Device short name | GoPact MCCB 250B |
Device application | Distribution |
Poles description | 3P /4P |
Protected poles description | 3P 3d /4P 3d |
[In] rated current | 250 A at 40 °C |
Network type | AC /DC |
[Ue] rated operational voltage | 415 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
Trip unit name | TM-D |
Trip unit technology | Thermal-magnetic |
Trip unit rating | 250 A |
Long-time pick-up adjustment type Ir (thermal protection) | Adjustable/Fixed |
[Ir] long-time protection pick-up adjustment range | 0.7...1 x In/ 1 x In |
[Ui] rated insulation voltage | 440 V AC conforming to EN/IEC 60947-2 |
Connection pitch | 35 mm |
Breaking capacity [Icu] | 25 kA Icu at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 36 kA Icu at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
[Ics] rated service breaking capacity | 25 kA at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 36 kA at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
Mechanical durability | 25,000 cycles |
Electrical durability | 8000 cycles at 415 V In |
Protection type | L : for overload protection (thermal) I : for short-circuit protection (magnetic) |
Dimensions (mm) (HxWxD) | 3P /165x105x90 mm 4P/165x140x90 mm |
Net weight (Kg) | 3P/1.9Kg 4P/2.4 Kg |
Door cutout Dimensions (WxH) | 3P/89x72.4mm 4P/89x72.4mm |