Motor circuit breaker, TeSys GV2, 3P, 1-1.6 A, thermal magnetic, screw clamp terminals.
| Specifications |
| Range | TeSys GV2 TeSys Deca |
| Country of Origin (Estimated) | Thailand (Other) |
| Warranty | 12 months |
| CO/CQ | Yes (if) |
| Product name & Device short name | GV2P |
| Device application | Motor protection |
| Trip unit technology | Thermal-magnetic |
| Poles description | 3P |
| Motor power kW | 0.37 kW at 400/415 V AC 50/60 Hz 0.55 kW at 400/415 V AC 50/60 Hz |
| Breaking capacity | 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
| Control type | Rotary handle |
| [In] rated current | 1.6A |
| Thermal protection adjustment range | 1…1.6 A conforming to IEC 60947-4-1 |
| Magnetic tripping current | 22.5 A |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
Dimensions (mm) (WxHxD) | 45x89x97 mm |