| Specifications | 
| Range of product | EasyLogic PM2200 | 
| Country of Origin (Estimated) | India | 
| Warranty | 12 months | 
| CO/CQ | Yes (if) | 
| Product name & Device short name | PM2230 | 
| Product or component type | Power meter | 
| Power quality analysis | Total harmonic distortion up to the 31st harmonic
 | 
| Device application | Sub billing Power monitoring
 | 
| Type of measurement | Apparent power min/max, total Active and reactive power min/max, total
 Current min/max, avg
 Voltage min/max, avg
 Frequency min/max, avg
 Total current harmonic distortion THD (I) per phase
 Total voltage harmonic distortion THD (U) per phase
 Power factor min/max, avg
 Apparent energy total
 Active and reactive energy total
 | 
| Metering type | Calculated neutral current Active power P, P1, P2, P3
 Current I, I1, I2, I3
 Peak demand power PM, QM, SM
 Voltage U, U21, U32, U13, V, V1, V2, V3
 Peak demand currents
 Reactive power Q, Q1, Q2, Q3
 Demand power P, Q, S
 Unbalance current
 Active, reactive, apparent energy (signed, four quadrant)
 Apparent power S, S1, S2, S3
 | 
| [Us] rated supply voltage | 35…480 V AC 50/60 Hz between phases 20…277 V AC 50/60 Hz between phase and neutral
 480…999000 V AC 50/60 Hz with external VT
 | 
| [In] rated current | 5 A 1 A
 | 
| Display type and colour | Backlit LCD and Monochrome | 
| Display resolution | 128 x 128 pixels | 
| Communication port protocol | Modbus RTU at 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps even/odd or none - 2 wires, insulation 2500 V | 
| Communication port support | Screw terminal block: RS485 | 
| Data recording | Energy consumption logs Power logs
 Time stamping
 Min/max for 8 parameters
 | 
| Function available | Real time clock | 
| Measurement current | 5…6000 mA | 
| Measurement voltage | 35…480 V AC 50/60 Hz between phases 20…277 V AC 50/60 Hz between phase and neutral
 480…999000 V AC 50/60 Hz with external VT
 | 
| Frequency measurement range | 45…65 Hz | 
| [Us] rated supply voltage | 80...277 V AC 45...65 Hz +/- 10 % 100...277 V DC +/- 10 %
 | 
| Measurement accuracy | Apparent power +/- 0.5 % Active energy +/- 0.5 %
 Reactive energy +/- 1 %
 Active power +/- 0.5 %
 Voltage +/- 0.5 %
 Power factor +/- 0.01
 Current +/- 0.5 %
 Frequency +/- 0.05 %
 | 
| Accuracy class | Class 1 reactive energy conforming to IEC 62053-24 Class 0.5S active energy conforming to IEC 62053-22
 Class 5 harmonic distorsion (I THD & U THD)
 | 
| Material | Polycarbonate | 
| Dimensions (mm) (H x W x D)
 | 96x96x61.64mm | 
| Cut-out dimensions | 92 x 92 mm | 
| Net weight | 300 g |