Three-phase monitoring relay (Phase failure detection, sequence monitoring, Over- and undervoltage monitoring) 2C/O, 0,0.1-30s, L1-L2-L3=3x300-500VAC (CM-PVS.41S)
Specifications | 1SVR730794R3300 |
Extended Product Type | CM-PVS.41S |
Country of Origin (Estimated) | Germany (Other) |
Warranty | 12 months |
CO/CQ | Yes (if) |
Product or component type | Three-phase Monitoring Relay |
Function | Phase failure detection Phase sequence monitoring Over- and undervoltage monitoring |
Measuring Range | (L-L) 300 ... 500 V AC |
Time Range | ≤ 200 ms start-up delay 0 s or 0.1 ... 30 s tripping delay (ON or OFF) |
Rated Control Supply Voltage (Us) | (L-L) 300 ... 500 V AC |
Output | 2 c/o (SPDT) contacts |
Terminal Type | Screw Terminals |
Rated Operational Current AC-12 (Ie) | (230 V) 4 A |
Rated Operational Current DC-12 (Ie) | (24 V) 4 A |
Rated Insulation Voltage (Ui) | Input Circuit / Output Circuit 600 V Output Circuit 1 / Output Circuit 2 300 V |
Electrical Durability | AC-12 100000 cycle |
Mechanical Durability | 30000000 cycle |
Tightening Torque | 0.6 ... 0.8 N·m |
Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
Standards | CAN/CSA C22.2 No.14 IEC/EN 63000 IEC/EN 60255-27 IEC/EN 61000-6-2 IEC/EN 61000-6-3 UL 508 |
Dimensions (WxHxD) | 22.5 x 85.6 x 103.7 mm |
Net weight | 0.139 Kg |